This Honeywell product is R7140G, L, M Burner Control Modules, are microprocessor-based integrated burner control for automatically fired gas, oil or combination fuel single burner applications. Functions provided by the R7140G, L, M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
Please see Extended Information Tab for Literature
Application |
Upgrade Replacement Programming Control for R4140 or BC7000 |
Flame Establishing Period - Pilot |
4 sec or 10 sec |
Flame Establishing Period - Main |
10 sec, or 15 sec, or 30 sec, or Intermittent |
Required Components |
R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. ST7800 Plug-in Purge Timer Card. |
Voltage |
120 Vac (+10, -15%) |
Vibration |
0.5 G environment |
Early Spark Termination |
Yes, 5 sec |
Ambient Temperature Range (F) |
-40 F to +140 F |
Dimensions (in.) |
7 in. wide x 6 5/32 high x 5 3/4 in. deep |
Technical Information: